-is a coaxial narrowband surge protection BrOK®, type PKO-N-lambda-120M-BCD/F-F is a typ 1+2+3 (lightning current drain + surge arester+fine protection), operating on the principle of a short-circuited quarter resonator tuned to the center of the frequency band 120 MHz. The protections can be used to protect 50 Ω coaxial cables equipped with type N connectors leading to or from the outside installations protected against direct lightning strike LPZ (lightning protection zone) 0B,C,D and equipment connected to these cable installations.

                                        Specification of coaxial narrowband surge protection BrOK®, type PKO-N-lambda-120M-BCD/F-F

The coaxial narrowband surge protection BrOK®, type PKO-N-lambda-120M-BCD/F-F is a typ 1+2+3 (lightning current drain + surge arester+fine protection), operating on the principle of a short-circuited quarter resonator tuned to the center of the frequency band 2,4 GHz. The protections can be used to protect 50 Ω coaxial cables equipped with type N connectors leading to or from the outside installations protected against direct lightning strike LPZ (lightning protection zone) 0B,C,D and equipment connected to these cable installations.

The surge protections guard against the impact of the electromagnetic impulses associated with the atmospheric discharges during lightning storms. The surge protections guard equipment and instruments against damages usually caused by direct lightning strike of the coaxial cable as specified by IEC 61312-1 (tested by current surge wave of 2.5 kA and duration of 10/350 µs).

In order to facilitate proper functioning of any surge protection it is important to provide an adequate connection to the equi-potential lead of the protected system EP. This connection must be made using a copper conductor of at least 2.5 mm2. The protection is simply inserted in the line using connectors type N/F-F. Rugged construction of the protections assures reliable drainage of lightning currents thus protecting the equipment against thermal destruction. The effectiveness of the BrOK® protections allows them to be installed even in enclosures constructed using thermo-plastic materials.

Type description: PKO-N-lambda-120M-BCD/F-F, see fig.1

Catalog Number: pkon120mbcd/ff

Technical parameters of protection:

Bandwidth of protection: 107 - 144 MHz
Max. residual voltage on the protected output with IZRP applied: see fig.2
Attenuation and reflection coefficient in the working bandwidth: see fig.3
Test current impulse IZRP: 2,5 kA for pulse of 10/350 µs
Maximum voltage on the protected output:  < ± 52 Vp-p 

The way how to connect a surge absorber into a signal path:

- as a cable through-junction by connectors N/F-F

- to an equipotential busbar of EP object by the stranded Cu conductor with the minimal cross-section of 2,5mm2 with molded cable eye and M5 bolt 

Mounting position: any                        Weight: 107 g                              Cover class: IP20

Fig.1 

pko n 120m b ff

 

  1 pko n 120M bcd ff
Fig.2 Shows the trace of the residual voltage present on the output of the coaxial narrowband surge protection BrOK®,

type PKO-N-lambda-120M-BCD/F-F when subjected to a transient current wave of 2.5 kA, 10/350 µs.

2 pko n 120m bcd ff
Fig.3 The attenuation and reflection characteristic of the coaxial narrowband surge protection BrOK®,

type PKO-N-lambda-120M-BCD/F-F when measured in the band from 50 MHz to 240 MHz.

Analyzer Setting:

Attenuation: 0,5 dB/div (yelow curve)

Reflection coefficient: 10 dB/div (green curve)

Cursor set at: 107 MHz

The certificate of conformance was issued based on test protocol No: P 02/01/37 generated by certified test laboratory No: 1148,ABEGU Co., Zkusebna, Czech Republic.

The overvoltage protection is made under utility design č.: 10494

The Warranty period is 24 months from the date of date of sale. In case of doubt is the condition of the warranty acceptation the check on place of instalation by our serviceman and the label type be intact. By the warranty period duration is possible to supply an spare surge absorber of a same type.

  The technical consultation and a service is provide by the company:

                                                                                      Ing. Vladimír Brok, Jiráskovo nábřeží 717, 468 22 Železný Brod, Česká republika

Business and a technical informations:

                                                                      cell phone: VoIP: +420484351351, mobil:+420604489036, e-mail: This email address is being protected from spambots. You need JavaScript enabled to view it. www.prepeti.cz

Surge absorbers BrOK®-the quality for a reasonable price.

Your question